Columbia Accident Investigation Board Report, Volume I

TEMPERATURE (F)

TEMPERATURE (F)

  • 0 50 100 150 200 250 300 — 350

Time (seconds from EI)

Figure 3.6-5. The analysis of the effect of a 10-inch hole in RCC panel 8 on Sensor 2 from EI to EI+500 seconds. The jagged line shows the actual flight data readings and the smooth line the calculated result for a 10-inch hole with some sneak flow of superheated air behind the spar insulation.

left wing leading edge spar, recorded the beginning of a gradual and abnormal rise in temperature from an expected

30 degrees Fahrenheit to 65 degrees at EI+493, when it then 107

073 dropped to "off-scale low," a reading that drops off the scale 090 at the low end of the sensorʼs range (see Figure 3.6-4). Sen- 109 sor 2, one of the first to fail, did so abruptly. It had indicated

only a mild warming of the RCC attachment clevis before the signal was lost.

A series of thermal analyses were performed for different

sized holes in RCC panel 8 to compute the time required to heat Sensor 2 to the temperature recorded by the Modular

Auxiliary Data System. To heat the clevis, various insula-

  • 900 — 1000

tors would have to be bypassed with a small amount of

59:09 leakage, or "sneak flow." Figure 3.6-5 shows the results of

these calculations for, as an example, a 10-inch hole, and demonstrates that with sneak flow around the insulation, the temperature profile of the clevis sensor was closely matched by the engineering calculations. This is consistent with the same sneak flow required to match a similar but abnormal ascent temperature rise of the same sensor, which further supports the premise that the breach in the leading edge of the wing occurred during ascent. While the exact size of the breach will never be known, and may have been smaller or larger than 10 inches, these analyses do provide a plausible explanation for the observed rises in temperature sensor data during re-entry.

Investigators initially theorized that the foam might have broken a T-seal and allowed superheated air to enter the wing between the RCC panels. However, the amount of T-seal debris from this area and subsequent aerothermal analysis showing this type of breach did not match the observed damage to the wing, led investigators to eliminate a missing T-seal as the source of the breach.

Although abnormal, the re-entry temperature rise was slow and small compared to what would be expected if Sensor 2 were exposed to a blast of superheated air from an assumed breach in the RCC panels. The slow temperature rise is at-

V07T9666A – Left Wing Lower Surface Temperature

OSH

Degrees F

1000 STS - 107

STS - 073 STS - 090

EI+496 STS - 109

450 500 0 OSL

  • 0 100 200 300 400 500 600 700 800 900 — 1000

Time (seconds from EI)

Figure 3.6-6. As early as EI+370, Sensor 3 began reading significantly higher than on previous flights. Since this sensor was located in a thermal tile on the lower surface of the left wing, its temperatures are much higher than those for the other sensors.

67

tributed to the presence of a relatively modest breach in the RCC, the thick insulation that surrounds the sensor, and the distance from the site of the breach in RCC panel 8 to the clevis sensor.

The readings of Sensor 3, which was in a thermal tile, began rising abnormally high and somewhat erratically as early as EI+370, with several brief spikes to 2,500 degrees

Fahrenheit, significantly higher than the 2,000-degree peak temperature on a normal re-entry (Figure 3.6-6). At EI+496, this reading became unreliable, indicating a failure of the wire or the sensor. Because this thermocouple was on the wing lower surface, directly behind the junction of RCC panel 9 and 10, the high temperatures it initially recorded were almost certainly a result of air jetting through the damaged area of RCC panel 8, or of the normal airflow being disturbed by the damage. Note that Sensor 3 provided an external temperature measurement, while Sensors 2 and 4 provided internal temperature measurements.

Sensor 4 also recorded a rise in temperature that ended in an abrupt fall to off-scale low. Figure 3.6-7 shows that an abnormal temperature rise began at EI+425 and abruptly fell at EI+525. Unlike Sensor 2, this temperature rise was extreme, from an expected 20 degrees Fahrenheit at EI+425 to 40 degrees at EI+485, and then rising much faster to 120 degrees at EI+515, then to an off-scale high (a reading that climbs off the scale at the high end of the range) of 450 degrees at EI+522. The failure pattern of this sensor likely indicates destruction by extreme heat.

The timing of the failures of these four sensors and the path of their cable routing enables a determination of both the timing and location of the breach of the leading edge spar, and indirectly, the breach of the RCC panels. All the cables from these sensors, and many others, were routed into wiring harnesses that ran forward along the back side of the leading edge spar up to a cross spar (see Figure 3.6-8), where they passed through the service opening in the cross spar and then ran in front of the left wheel well before reaching interconnect panel 65P, where they entered the fuselage. All sensors with wiring in this set of harnesses failed between EI+487 to EI+497, except Sensor 4, which survived until

EI+522. The diversity of sensor types (temperature, pressure, and strains) and their locations in the left wing indicates that they failed because their wiring was destroyed at spar burn-through, as opposed to destruction of each individual sensor by direct heating.

Examination of wiring installation closeout photographs (pictures that document the state of the area that are normally taken just before access is closed) and engineering drawings show five main wiring harness bundles running forward along the spar, labeled top to bottom as A through E (see Figure 3.6-8). The top four, A through D, are spaced 3 inches apart, while the fifth, E, is 6 inches beneath them. The separation between bundle E and the other four is consistent with the later failure time of Sensor 4 by 25 to 29 seconds, and indicates that the breach was in the upper two-thirds of the spar, causing all but one of the cables in this area to fail between EI+487 to EI+497. The breach then expanded vertically, toward the underside of the wing, causing Sensor 4 to fail 25 seconds

V09T9895A – Left Wing Front Spar Panel 9 Temperature

OSH

400 EI+522

STS - 107

STS - 073 STS - 090

STS - 109

Degrees F

-100

-200 OSL

-300

  • 0 100 200 300 400 500 600 700 800 900 — 1000

Time (seconds from EI)

Figure 3.6-7. Sensor 4 also began reading significantly higher than previous flights before it fell off-scale low. The relatively late reaction of this sensor compared to Sensor 2, clearly indicated that superheated air started on the outside of the wing leading edge spar and then moved into the mid-wing after the spar was burned through. Note that immediately before the sensor (or the wire) fails, the temperature is at 450 degrees Fahrenheit and climbing rapidly. It was the only temperature sensor that showed this pattern.

later. Because the distance between bundle A and bundle E is 9 inches, the failure of all these wires indicates that the breach in the wing leading edge spar was at least 9 inches from top to bottom by EI+522 seconds.

Sensor 5 V07P8010A V07P8010A

Panel

  • Panel — 98

9 Panel Panel

  • Panel — 88

9 Panel

A B C D

E Sensor 4 V09T9895A V09T9895A

Sensor 6 V07P8058A V07P8058A

Figure 3.6-8. The left photo above shows the wiring runs on the backside of the wing leading edge behind RCC panel 8 – the circle marks the most likely area where the burn through of the wing leading edge spar initially occurred at EI+487 seconds. The right photo shows the wire bundles as they continue forward behind RCC panels 7 and 6. The major cable bundles in the upper right of the right photo carried the majority of the sensor data inside the wing. As these bundles were burned, controllers on the ground began seeing off-nominal sensor indications.

68

Also directly behind RCC panel 8 were pressure sensors V07P8010A (Sensor 5), on the upper interior surface of the wing, and V07P8058A (Sensor 6), on the lower interior surface of the wing. Sensor 5 failed abruptly at EI+497. Sensor 6, which was slightly more protected, began falling at EI+495, and failed completely at EI+505. Closeout photographs show that the wiring from Sensor 5 travels down from the top of the wing to join the uppermost harness, A, which then travels along the leading edge spar. Similarly, wiring from Sensor 6 travels up from the bottom of the wing, joins harness A, and continues along the spar. It appears that Sensor 5ʼs wiring, on the upper wing surface, was damaged at EI+497, right after Sensor 1 failed. Noting the times of the sensor failures, and the locations of Sensors 5 and 6 forward of Sensors 1 through 4, spar burn-through must have occurred near where these wires came together.

Two of the 45 left wing strain gauges also recorded an anomaly around EI+500 to EI+580, but their readings were not erratic or off-scale until late in the re-entry, at EI+930. Strain gauge V12G9048A was far forward on a cross spar in the front of the wheel well on the lower spar cap, and strain gauge V12G9049A was on the upper spar cap. Their responses appear to be the actual strain at that location until their failure at EI+935. The exposed wiring for most of the left wing sensors runs along the front of the spar that crosses in front of the left wheel well. The very late failure times of these two sensors indicate that the damage did not spread into the wing cavity forward of the wheel well until at least EI+935, which implies that the breach was aft of the cross spar. Because the cross spar attaches to the transition spar behind RCC panel 6, the breach must have been aft (outboard) of panel 6. The superheated air likely burned through the outboard wall of the wheel well, rather than snaking forward and then back through the vent at the front of the wheel well. Had the gases flowed through the access opening in the cross spar and then through the vent into the wheel well, it is unlikely that the lower strain gauge wiring would have survived.

Left OMS Pod Surface Mounted Tile Temperature on Forward Looking Face

49:49

STS - 090

V07T9913

V07T9913 V07T9913

V07T9913 V07T9913 V07T9913

V07T9913 V07T9913 V07T9913

Degrees F

  • 0 100 200 300 400 500 — 600

44:09 Time (seconds from EI)

Figure 3.6-9. Orbital Maneuvering System (OMS) pod heating was initially significantly lower than that seen on previous Columbia missions. As wing leading edge damage later increased, the OMS pod heating increased dramatically. Debris recovered from this area of the OMS pod showed substantial pre-breakup heat damage and imbedded drops of once-molten metal from the wing leading edge in the OMS pod thermal tiles.

Finally, the rapid rise in Sensor 4 at EI+425, before the other sensors began to fail, indicates that high temperatures were responsible. Comparisons of sensors on the outside of the wing leading edge spar, those inside of the spar, and those in the wing and left wheel well indicate that abnormal heating first began on the outside of the spar behind the RCC panels and worked through the spar. Since the aluminum spar must have burned through before any cable harnesses attached to it failed, the breach through the wing leading edge spar must have occurred at or before EI+487.

Other abnormalities also occurred during re-entry. Early in re-entry, the heating normally seen on the left Orbital Maneuvering System pod was much lower than usual for this point in the flight (see Figure 3.6-9). Wind tunnel testing demonstrated that airflow into a breach in an RCC panel would then escape through the wing leading edge vents behind the upper part of the panel and interrupt the weak aerodynamic flow field on top of the wing. During re-entry, air normally flows into these vents to equalize air pressure across the RCC panels. The interruption in the flow field behind the wing caused a displacement of the vortices that normally hit the leading edge of the left pod, and resulted in a slowing of pod heating. Heating of the side fuselage slowed, which wind tunnel testing also predicted.

To match this scenario, investigators had to postulate damage to the tiles on the upper carrier panel 9, in order to allow sufficient mass flow through the vent to cause the observed decrease in sidewall heating. No upper carrier panels were found from panels 9, 10, and 11, which supports this hypothesis. Although this can account for the abnormal temperatures on the body of the Orbiter and at the Orbital Maneuvering System pod, flight data and wind tunnel tests confirmed that this venting was not strong enough to alter the aerodynamic force on the Orbiter, and the aerodynamic analysis of mission data showed no change in Orbiter flight control parameters during this time.

During re-entry, a change was noted in the rate of the temperature rise around the RCC chin panel clevis temperature sensor and two water supply nozzles on the left side of the fuselage, just aft of the main bulkhead that divides the crew cabin from the payload bay. Because these sensors were well forward of the damage in the left wing leading edge, it is still unclear how their indications fit into the failure scenario.

Sensor Loss and the Onset of Unusual Aerodynamic

Effects (EI+500 through EI+611)

Fourteen seconds after the loss of the first sensor wire on the wing leading edge spar at EI+487, a sensor wire in a bundle of some 150 wires that ran along the upper outside corner of the left wheel well showed a burn-through. In the next 50 seconds, more than 70 percent of the sensor wires in three cables in this area also burned through (see Figure 3.6-10). Investigators plotted the wiring run for every left-wing sensor, looking for a relationship between their location and time of failure.

Only two sensor wires of 169 remained intact when the Modular Auxiliary Data System recorder stopped, indicat-Percent Loss of Sensor Signals Versus Time In Left Wing and Wing Leading Edge Wire Bundles

69

V09T9895A

Leading Edge (18 of 18)

Bundle 1

Wheel Well

Quantity of Sensor Signals Lost - %

70 Bit Flip

Left Elevon 60 Accel Response

1st Wheel Well Temp Rise 50 (1700,1702 Bit change)

1st OI Starts Failure

40 L Elevon Accel Fail

  • 450 500 — 550

Sensors with Cables Along Loading Edge Start Loss 14 sec Earlier Than the 3 Bundles

Figure 3.6-10. This chart shows how rapidly the wire bundles in the left wing were destroyed. Over 70 percent of the sensor wires in the wiring bundles burned through in under a minute. The black diamonds show the times of significant timeline sensor events.

ing that the burn-throughs had to occur in an area that nearly every wire ran through. To sustain this type of damage, the wires had to be close enough to the breach for the gas plume to hit them. Arc jet testing (in a wind tunnel with an electrical arc that provides up to a 2,800-degree Fahrenheit airflow) on a simulated wing leading edge spar and simulated wire bundles showed how the leading edge spar would burn through in a few seconds. It also showed that wire bundles would burn through in a timeframe consistent with those seen in the Modular Auxiliary Data System information and the telemetered data.

Later computational fluid dynamics analysis of the mid-wing area behind the spar showed that superheated air flowing into a breached RCC panel 8 and then interacting with the internal structure behind the RCC cavity (RCC ribs and spar insulation) would have continued through the wing leading edge spar as a jet, and would have easily allowed superheated air to traverse the 56.5 inches from the spar to the outside of the wheel well and destroy the cables (Figure 3.6-11). Controllers on the ground saw these first anomalies in the telemetry data at EI+613, when four hydraulic sensor cables that ran from the aft part of the left wing through the wiring bundles outside the wheel well failed.

Aerodynamic roll and yaw forces began to differ from those on previous flights at about EI+500 (see Figure 3.6-12). Investigators used flight data to reconstruct the aerodynamic forces acting on the Orbiter. This reconstructed data was then compared to forces seen on other similar flights of Columbia

Bundle 3 (115 of 117) V07P8049A Bundle 4 (25 of 25)

V07P9197A

Starts Failure

1st Orbiter Debris Event

Reversal of Roll Moment and start of Slow Aileron Trim Change

Start LMG Struct Actuator Temp Rise

6th OI Starts Failure 7th OI Starts Failure tion for 3 Bundles

  • 600 650 700 750 — 800

ime (seconds from EI) mph

Flow

Contours of Velocity Magnitude (fps) Jun 10, 2003 FLUENT 6.1 (2d, coupled imp, ske)

Figure 3.6-11. The computational fluid dynamics analysis of the speed of the superheated air as it entered the breach in RCC panel 8 and then traveled through the wing leading edge spar. The dark- est red color indicates speeds of over 4,000 miles per hour. Temperatures in this area likely exceeded 5,000 degrees Fahrenheit. The area of detail is looking down at the top of the left wing.

70

STS 107 Delta Rolling/Yawing Moment Coefficients

0.0025

Delta Cll (Roll Moment)

Delta Cln (Yaw Moment)

0.0020 Delta Cll Aero Model

Delta Cln Aero Model

Initial Roll

Delta Roll/Yaw Moment Coefficient

Wing Frnt Spar Panel 9 Temp

0.0015 - 13:49:32 Wing LE 55 LWR Att. Clevis

RCC 10 - Start Off Nominal Trend - 13:52:56 Hydraulic System Left OUTBD / INBD Actuator Temp Increase - 13:51:14

0.0010

0.0005

0.000

-0.0005

  • 13:50:19

-0.0010 Left OMS Pod TC BP 0731T - Start Off Nominal Trend

  • Reduced Rise Rate

  • 13:49:49

-0.0015 Left OMS Pod LRSI Surface Temp

Left OMS Pod TC BP0732T Left OMS Pod TC BP0749T

  • Start Off Nominal Trend - Reduced Rise Rate -0.0020 - 13:49:59

Left PLBD Surface TC BP3703T

  • Start Off Nominal Trend
  • Reduced Rise Rate -0.0025 - 13:50:09

49:00.0 50:00.0 51:00.0

Figure 3.6-12. At approximately EI+500 seconds, the aerodynamic roll and yaw forces began to diverge from those observed on previous flights. The blue line shows the Orbiterʼs tendency to yaw while the red line shows its tendency to roll. Nominal values would parallel the solid black line. Above the black line, the direction of the force is to the right, while below the black line, the force is to the left.

and to the forces predicted for STS-107. In the early phase of fight, these abnormal aerodynamic forces indicated that Columbiaʼs flight control system was reacting to a change in the external shape of the wing, which was caused by pro- gressive RCC damage that caused a continuing decrease in lift and a continuing increase in drag on the left wing.

Between EI+530 and EI+562, four sensors on the left inboard elevon failed. These sensor readings were part of the data telemetered to the ground. Noting the system failures, the Maintenance, Mechanical, and Crew Systems officer notified the Flight Director of the failures. (See sidebar in Chapter 2 for a complete version of the Mission Control Center conversation about this data.)

At EI+555, Columbia crossed the California coast. People on the ground now saw the damage developing on the Orbiter in the form of debris being shed, and documented this with video cameras. In the next 15 seconds, temperatures on the fuselage sidewall and the left Orbital Maneuvering System pod began to rise. Hypersonic wind tunnel tests indi-

Off-Nominal Roll & Yaw

LMG Brake Line Temps Start Off Nominal Trend Temperature Rise Rate Change - Hyd Sys 1 LMG UpLK UnIK Ln Temp - 13:52:41 - Sys 3 LMG Brake Ret Line Temp 2 Temp Sensors Begin Off Nominal Response - LMG Brake Line Temp B, C Left Lower Wing Skin Temp - 13:56:16/22 - V09T9895A - Wing Front Spar Panel 9 - OSL - 13:57:28 - V09T9849A - OB Elevon, Lower Surface Left Upper Wing Skin Temp - 13:52:49.5/51.4 Left Upper Wing Skin Temp - OSL - 13:57:43 - Begin Off Niminal Trend

  • 13:56:24 vis Left INBD Elevon Lower Skin Temp
  • Start of Off Nominal Trend Left Main Gear Strut Start Sharp Aileron Trim

Elevon Return Line Temps - OSL - Temp Rise Rate Chg - 13:58:03 - 13:53:10 / 36 - 13:56:53 Sys 2 LH Brake 4 Left OMS Pod Surf Temp - Change in Existing Viv Return Temp Start Slow Alllegron Debris #11 MLG LH OB Tire - Start of sharp Off Nominal Trend Trim Change Dwnrd. Temp - 13:55:36/42 Pressure #1, #2 - 13:52:39/ 53:09 - 13:54:20 - 13:59:22 - Start Off Nom Debris #15 - 13:57:19/24 Alpha Mod Debris #9, #10 - 13:56:09/13 MLG LH OutBD & Active - 13:55:25/30 INBD Tire Pressure #1 - 13:53:31 - Pressure Trend to OSL - 13:58:32 Fuse Side Surf Temp Fuse Low Surf BF Temp Fuse Side Surf TC & - Start Off Nom Trend Left PLBD Surface TC - 13:57:09 - Temp Increase to OSH - 13:59:29

wer Surface TC ff Nominal BFS Fault Message (4) ncrease Tire Pressures 9 Debris #1

Debris #7 - 13:58:40/56 - 13:53:44/48 - 13:55:04/10

Debris #2 1st Roll Reversal Initiation - 13:56:30 Mid Fuselage Bondline Temp Left Main Gear - 13:53:46/50 Complete - 13:46:55 & LH Aft Fus Sidewall Temp Downlock Indication Debris #3 - Off Nominal - Transferred ON - 13:53:54/58 - 13:54:22 - 13:59:06

Debris #4

  • 13:54:00/04 Debris #13, #14 Flash #1

LMG Brake Line Temp (D) Debris #5 - 13:54:33.3 - 13:55:55/59 Flash #1, #2

  • Start Off Nominal Trend - 13:54:07/11 Debris #6 - 13:57:53.7 - 13:52:17 - 13:54:35/37 Debris #12 - 13:57:59.5

Left Wing Spar Cap - 13:55:45/ Flash #2

  • Off Nominal Strain Increase LMG Brake Line Temp B Debris #8 - 13:57:59.5 Debris #7 - 13:52:18 - Off Nominal Trend - 13:55:21/27 58:01.5 - 13:57:19/29 - 13:54:10

0 52:00.0 53:00.0 54:00.0 55:00.0 56:00.0 57:00.0 58:00.0 59:00.0 00:00.0

Time (min:sec)

substantial leading edge damage around RCC panel 9. Data on Orbiter temperature distribution as well as aerodynamic forces for various damage scenarios were obtained from wind tunnel testing.

Figure 3.6-13 shows the comparison of surface temperature distribution with an undamaged Orbiter and one with an entire panel 9 removed. With panel 9 removed, a strong vortex flow structure is positioned to increase the temperature on the leading edge of the Orbital Maneuvering System pod. The aim is not to demonstrate that all of panel 9 was missing at this point, but rather to indicate that major damage to panels near panel 9 can shift the strong vortex flow pattern and change the Orbiterʼs temperature distribution to match the Modular Auxiliary Data System information. Wind tunnel tests also demonstrated that increasing damage to leading edge RCC panels would result in increasing drag and decreasing lift on the left wing.

Recovered debris showed that Inconel 718, which is only found in wing leading edge spanner beams and attachment

cated that the increased heating on the Orbital Maneuvering fittings, was deposited on the left Orbital Maneuvering Sys- System pod and the roll and yaw changes were caused by tem pod, verifying that airflow through the breach and out of the upper slot carried molten wing leading edge material back to the pod. Temperatures far exceeded those seen on previous re-entries and further confirmed that the wing leading-edge damage was increasing.

71

By this time, superheated air had been entering the wing since EI+487, and significant internal damage had probably occurred. The major internal support structure in the mid-wing consists of aluminum trusses with a melting point of 1,200 degrees Fahrenheit. Because the ingested air may have been as hot as 8,000 degrees near the breach, it is likely that the internal support structure that maintains the shape of the wing was severely compromised.

As the Orbiter flew east, people on the ground continued to record the major shedding of debris. Investigators later scrutinized these videos to compare Columbiaʼs re-entry with recordings of other re-entries and to identify the debris. The video analysis was also used to determine additional search areas on the ground and to estimate the size of various pieces of debris as they fell from the Orbiter.

Temperatures in the wheel well began to rise rapidly at EI+601, which indicated that the superheated air coming through the wing leading edge spar had breached the wheel well wall. At the same time, observers on the ground noted additional significant shedding of debris. Analysis of one of these "debris events" showed that the photographed object could have weighed nearly 190 pounds, which would have significantly altered Columbiaʼs physical condition.

At EI+602, the tendency of the Orbiter to roll to the left in response to a loss of lift on the left wing transitioned to a right-rolling tendency, now in response to increased lift on the left wing. Observers on the ground noted additional significant shedding of debris in the next 30 seconds. Left yaw continued to increase, consistent with increasing drag on the left wing. Further damage to the RCC panels explains the increased drag on the left wing, but it does not explain the sudden increase in lift, which can be explained only by some other type of wing damage.

Investigators ran multiple analyses and wind tunnel tests to understand this significant aerodynamic event. Analysis showed that by EI+850, the temperatures inside the wing

Run 12

Baseline smooth

RCC #9

TC 1106 removed TC 1724

Effect of Missing RCC Panel on Orbiter RELATIVE HEATING RATE Mid-Fuselage Thermal Mapping

0 0.1 0.2 0.3 0.4 0.5

Figure 3.6-13. The effects of removing RCC panel 9 are shown in this figure. Note the brighter colors on the front of the OMS pod show increased heating, a phenomenon supported by both the OMS pod temperature sensors and the debris analysis.